3 March 2014

Tyco, VIGILANT MX4428 and F4000 Fire indicator Panels

Product Identifiers

Vigilant MX4428 & F4000 Fire Indicator Panels with MX4428 Firmware Versions 3.10 to 3.21 Used in predominately in commercial, industrial and government buildings

Supplier Contact

Tyco New Zealand Limited
17 Mary Muller Drive, Heathcote, Christchurch 8022, New Zealand

For more infomration got to at: http://www.tycosafetyproducts-anz.com/ 

Responsible Agency

https://www.mbie.govt.nz

The Hazard!

A software bug may result in an alarm failing to sound when required.

What to do...

Building Owners – immediately contact your fire alarm service company and ask (i) if they are aware of the issue (ii) what action they are taking to check your fire alarm system for the fault and (iii) if the fault is present whether they have taken steps to repair it. Fire Contractors - Check MX4428 and F4000 fire indicator panels to determine what firmware they version they run on. Contact Tyco New Zealand for (i) a database assessment tool to quickly identify vulnerable panels and (ii) obtain free replacement firmware V3.15NA or V3.22N.

Product Identifiers

Vigilant MX4428 & F4000 Fire Indicator Panels with MX4428 Firmware Versions 3.10 to 3.21 Used in predominately in commercial, industrial and government buildings

Supplier Contact

Tyco New Zealand Limited
17 Mary Muller Drive, Heathcote, Christchurch 8022, New Zealand

For more infomration got to at: http://www.tycosafetyproducts-anz.com/ 

Responsible Agency

https://www.mbie.govt.nz